Free Fan BHP Calculator. air power and brake horsepower from CFM, static (or total) pressure, and fan efficiency. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts air power and brake horsepower from CFM, static (or total) pressure, and fan efficiency. It is the Fan BHP tool in the fan group on ACH Calculator.
It is not motor FLA, a VFD sizing sheet, or a wire/breaker calculator. If you need those, open a related tool instead of stretching this identity.
The identity on screen is W = Q ΔP / η (units consistent; IP: BHP ≈ CFM × SP / (6356 η)). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: CFM, SP in. w.g., η (total or static — you pick), result BHP and kW. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
W = Q ΔP / η (units consistent;
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 2000 CFM at 1.5 in, η=0.65.
2) Comparing a cheap blower.
3) Motor 1.15 SF discussion — not calculated.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
2000 CFM
1.5 in
η=0.65
BHP ≈ 2000×1.5/(6356×0.65) ≈ 0.73 hp
Work the same arithmetic on paper; the live result should match within rounding.
The IP constant converting CFM×in. w.g. to horsepower. SI uses Q(m³/s)×ΔP(Pa)/η = watts.
Match the pressure you typed. Total efficiency goes with FTP.
Divide BHP by motor η, then by 0.746. Not on the electrical site’s wire tools.
Add 2–5% if you want a sketch. Type a lower η instead.
SP from a catalog at standard air needs a density correction at altitude.
fan-laws if you change speed.
Primary identity: W = Q ΔP / η (units consistent; IP: BHP ≈ CFM × SP / (6356 η)). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Fan BHP. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.