HVAC reference charts

Each chart is a discussion table plus when the row is the wrong job, a worked example, and a link to the live calculator. Not a copyrighted ASHRAE dump.

Open a chart when you want a band explained. Open the linked tool when your number is off the grid.

Room ACH rangesBedroom 2–4, office 2–6, tent ~60, ISO planning bands.Duct velocity bandsQuiet house fpm versus commercial trunks.CFM per tonAirflow chips once capacity exists.Airflow unitsExact factors for mixed-unit takeoffs.Bath exhaust discussion values50 / 20 CFM plus the live bath tool.Example Rp/Ra chips (not Table 6-1)Office and classroom teaching chips.Filter / grille face velocity300 fpm return talk and nominal in².Water ΔT versus GPM (100 kBTU/h)500 × GPM × ΔT worked at 100 kBTU/h.Air density versus altitude0.075 at sea level, ~0.062 in Denver.Capture / face talk50–100 fpm canopies, 100 fpm booths.ISO class names versus planning ACHPlanning ACH chips, not particle counts.Equal-friction talk0.08 in/100 ft residential default.

What this calculator does

These charts reprint small lookups the calculators already use: room ACH ranges, duct velocity bands, 400 CFM/ton, airflow unit pairs, bath 50/20 talk, and water ΔT versus GPM.

They are not photocopies of ASHRAE or IMC tables. For an arbitrary input, open the linked calculator.

How to use it

Pick a chart, read the row, then open the matching tool if your number is not in the table.

Values are rounded for reading. Live arithmetic belongs on the tool page.

Formula, units, and limits

Each table is one identity (ACH, fpm, CFM/ton, unit conversion, GPM). No extra safety factors are buried in the cells.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Use a chart when you want a common band without filling a form. Use a calculator when the input is off-grid.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

A residential supply talk of 700 fpm is on the duct-velocity chart; 412 CFM at that speed still needs duct-size.

50 CFM intermittent bath is on bath-exhaust; a 12×8×8 ft custom ACH is not — open bathroom-fan.

FAQ

Can I submit a chart with a permit?

No. Charts are teaching lookups.

ISO ACH rows?

Planning talk, not ISO 14644 particle limits.

Rp/Ra chips?

Teaching numbers. Type values from your licensed 62.1.

Altitude density?

A dry 70 °F sketch, not a weather file.

Why fewer charts than tools?

Only identities that people look up as a band get a table.

Units?

IP on the chart; SI on the linked tool.

References

Disclaimer

Rounded lookups. The calculator and the adopted standard prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.