Free Fitting loss Calculator. a fitting pressure drop from a user loss coefficient C and velocity (dynamic pressure). Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts a fitting pressure drop from a user loss coefficient C and velocity (dynamic pressure). It is the Fitting loss tool in the duct group on ACH Calculator.
It is not an ASHRAE Duct Fitting Database reprint or a manufacturer elbow table. If you need those, open a related tool instead of stretching this identity.
The identity on screen is ΔP = C × (ρ V² / 2). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: C (typed), V or CFM+size, air density default 0.075 lb/ft³. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
ΔP = C × (ρ V² / 2)
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) Elbow C=0.3 at 800 fpm.
2) Takeoff C=0.5.
3) Two elbows in series (add ΔP).
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
V = 800 fpm = 13.3 ft/s
ρ = 0.075
Pv = 0.040 in w.g.
C=0.3 → ΔP=0.012 in
Work the same arithmetic on paper; the live result should match within rounding.
From a fitting catalog or ASHRAE DB you are licensed to use. This page will not invent a 90° elbow C for every radius.
Pv = ρ V²/2. In IP HVAC, Pv (in. w.g.) ≈ (V/4005)² at standard air.
In series, add. Parallel paths need a network, not this page.
Same C; ΔP in Pa = C × 0.5 ρ V² with V in m/s.
A throttle damper C changes with angle. Type the C for that position.
Use the listed pressure drop, not a generic C, when you have it.
Primary identity: ΔP = C × (ρ V² / 2). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.