| Talk | in. w.g. / 100 ft |
|---|---|
| Quiet residential | 0.06–0.08 |
| Typical residential | 0.08–0.10 |
| Commercial mains | 0.10–0.30 |
Open duct size with f = 0.08 unless your spec states another rate. Open duct friction and TEL to turn rate into a drop. High f shrinks ducts and grows fan power and noise.
FAQ
Pa/m?
0.08 in/100 ft is about 0.65 Pa/m. Use SI on the tool rather than mixing.
Flex duct?
Often needs a higher f than smooth metal.
Available static?
Equal friction must still fit the fan’s leftover ESP after the coil and filter.
Manual D friction chart?
Copyrighted. This site uses a published power-fit, not a scanned chart.
Water pipes?
Open hydronic pipe. Feet of head is not in. w.g. / 100 ft of air.
Limits
Not a Darcy–Weisbach textbook chart dump.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.