Psychrometric Calculator

Free Psychrometric Calculator. moist-air properties from dry-bulb plus RH, dew point, or wet-bulb using public Magnus-type formulas. Runs in your browser; not a permit or a Manual J.

Updates in this browser · not a mechanical permit


Formula

Identity
e_s = 6.112 exp(17.62 t/(243.12+t)) hPa; W=0.622 e/(P−e); h=1.006 t + W(2501+1.86 t)
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

This page converts moist-air properties from dry-bulb plus RH, dew point, or wet-bulb using public Magnus-type formulas. It is the Psychrometric tool in the moisture group on ACH Calculator.

It is not a copyrighted ASHRAE psych chart image, a Mollier reprint, or a listed coil selection. If you need those, open a related tool instead of stretching this identity.

The identity on screen is e_s = 6.112 exp(17.62 t/(243.12+t)) hPa; W=0.622 e/(P−e); h=1.006 t + W(2501+1.86 t). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.

Related calculators on this site:

How to use it

Use the fields that match the job: DB, plus RH or DP or WB, pressure/altitude, results: RH, DP, WB, W, h, v, ρ. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

e_s = 6.112 exp(17.62 t/(243.12+t)) hPa; W=0.622 e/(P−e); h=1.006 t + W(2501+1.86 t)

Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 75 °F / 50% RH space.

2) Coil leaving 55 °F DB / 54 °F WB.

3) Denver pressure.

If the job is life-safety, sterile, or listed equipment, stop here and use the specification.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

t_db=23.9 °C (75 °F)

RH=50%

T_dp≈12.8 °C

W≈0.0092 kg/kg

Work the same arithmetic on paper; the live result should match within rounding.

FAQ

Which coefficients?

Magnus IAPWS-style 17.62 / 243.12 (°C) over water. Fine for HVAC, not a metrology lab.

Wet-bulb iteration?

The engine iterates enthalpy / saturation at T_wb. Twb is the adiabatic saturation sketch.

Chart image?

Not embedded. Numbers only.

Sea level?

Default 101.325 kPa. Type altitude on air-density/pressure.

IP vs SI?

Enter °F or °C; W in gr/lb or g/kg; h in BTU/lb or kJ/kg.

Ice bulb?

Below freezing the page still uses water coefficients unless you switch the frost chip — labeled as approximate.

References

Primary identity: e_s = 6.112 exp(17.62 t/(243.12+t)) hPa; W=0.622 e/(P−e); h=1.006 t + W(2501+1.86 t). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only for Psychrometric. Adopted mechanical codes, OEM curves and a licensed designer prevail.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.