Free Garage exhaust Calculator. a residential or small garage exhaust sketch from ACH or CFM per square foot. Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts a residential or small garage exhaust sketch from ACH or CFM per square foot. It is the Garage exhaust tool in the air group on ACH Calculator.
It is not a parking-garage CO demand-control design or a fire/smoke exhaust model. If you need those, open a related tool instead of stretching this identity.
The identity on screen is CFM = ACH × V / 60 or CFM = rate × area. Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: Garage L×W×H, ACH chip (e.g. 4–6) or CFM/ft², result CFM. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
CFM = ACH × V / 60 or CFM = rate × area
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) A 22×22×8 ft two-car garage at 4 ACH.
2) A workshop using 1 CFM/ft² as a user rate.
3) Attached garage odor control versus a parking structure.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
22×22×8 → 3872 ft³
6 ACH (workshop chip; 4/8 also common)
CFM = 6×3872/60 = 387 CFM
Work the same arithmetic on paper; the live result should match within rounding.
It is a common sketch, not IMC parking-garage ventilation. Attached residential garages often rely on weatherization and a transfer path, not this CFM.
Demand control belongs in parking structures. This page does not model CO.
Exhaust in winter is a heat load — open ventilation-load if you need BTU/h.
Not modeled. Follow the charging-equipment listing and the garage ventilation spec.
Area rates (CFM/ft²) show up in some commercial tables. ACH is volume-based. Pick the method your spec uses.
Natural ventilation openings are a different IMC path. Do not use this fan CFM for that.
Primary identity: CFM = ACH × V / 60 or CFM = rate × area. Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for Garage exhaust. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.