Usefpm sketchm/s
Residential supply trunk600–9003.0–4.6
Residential return trunk500–7002.5–3.6
Commercial main1000–15005.1–7.6
Quiet register / grille face300–5001.5–2.5
Return grille free-area talk~300~1.5

400 CFM in 10 in round is about 730 fpm (residential supply). 400 CFM in 6 in round is about 2,040 fpm (noise). Open duct velocity to invert Q, V and D, and duct size for 0.08 in/100 ft equal friction.

Face velocity on a grille is not trunk velocity. A 300 fpm return face needs much more area than a 700 fpm trunk carrying the same CFM.

FAQ

Why list m/s?

European specs often quote 3–5 m/s in occupied-branch ducts.

Kitchen grease?

Listed grease ducts have their own velocity and slope rules. Not this table.

Flex?

Treat flex as slower / higher friction than smooth metal at the same Q.

VAV maximum?

Use the maximum box CFM, not the minimum, when checking noise.

Can I exceed 1,500 fpm?

Some risers do. Budget fan power and silencers. This table is talk, not a license.

Limits

Not an NC catalog and not a fire-smoke damper schedule.

Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.