ERV HRV Size Calculator

Free ERV/HRV calculator. Ventilation from 0.03×area + 7.5×(bedrooms+1), then recovered heat = 1.08 × CFM × ΔT × effectiveness. Runs in your browser; not a permit.

Updates in this browser · not a mechanical permit


Formula

Identity
Q = 0.03 A + 7.5 (N_br + 1); q = 1.08 × Q × (T_in − T_out); recovered = q × ε; rated ≈ 1.25 × Q
Steps

Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.

What this calculator does

Ranking ERV and HRV pages start from the whole-house ventilation rate, 0.03 CFM per ft² plus 7.5 CFM per person counting one more person than there are bedrooms. They then add about 25% so the unit still delivers that rate after filters and ducts, and they turn the winter temperature difference into heat with 1.08 × CFM × ΔT. Sensible recovery near 70% is the preload; HVI listings they cite run about 55–85%.

Not a kitchen hood, not a dryer, and not a choice between an ERV core and an HRV core. The arithmetic is the same for both.

The 62.2 page stops at the CFM. This page keeps going into the heat the core returns and the rated CFM to shop for.

Related calculators on this site:

How to use it

Type floor area and bedrooms, or type a CFM if you already have the rate. Effectiveness, indoor temperature and outdoor temperature finish the heat. Example is 2,000 ft², 3 bedrooms, 70%, 70 °F indoors, 32 °F outdoors.

Floor area, bedrooms, optional CFM, sensible recovery %, indoor °F, outdoor °F.

Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.

Formula, units, and limits

Q = 0.03 A + 7.5 (N_br + 1); q = 1.08 × Q × (T_in − T_out); recovered = q × ε; rated ≈ 1.25 × Q

Recovery must be positive. A typed CFM overrides the area formula. Negative ΔT means the outdoor air is warmer than the house.

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Typical uses include:

1) 2,000 ft² and 3 bedrooms, the 90 CFM planning line.

2) A model at 60% or 80% instead of 70%.

3) A CFM you already calculated, typed over the area line.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

The Example button uses this set:

0.03×2,000 + 7.5×(3+1) = 90 CFM

1.08 × 90 × (70−32) = 3,694 BTU/h. At 70% that is 2,586 BTU/h recovered. Rated size ≈ 113 CFM.

FAQ

ERV or HRV?

The arithmetic is the same. Those pages pick an HRV for a cold dry winter and an ERV when the summer is humid. This page does not choose the core.

Why 70%?

A typical sensible recovery the sizing pages preload. Listings they cite run about 55–85%. Type the model’s number.

Why 1.25?

So the unit still meets the rate after filter and duct pressure. It is not a fan curve.

Same as 62.2?

The airflow line is that formula. The rest is the heat the core keeps.

Does it replace the hood?

No. Whole-home recovery does not replace a range hood or a dryer.

Where does 1.08 come from?

Standard-air sensible factor, BTU/h per CFM per °F. Same identity as the sensible-heat page.

References

Composite of ranking ERV/HRV sizing pages. The airflow line is the same 62.2 form as the whole-house page. 1.08 is the standard-air sensible factor. 1.25 is the margin those pages add for duct and filter pressure, not a fan curve. 70% is a typical sensible recovery, not a rating.

  • ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
  • International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
  • ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
  • ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
  • Magnus / WMO saturation vapor-pressure approximations for dew point.
  • Huebscher equivalent-diameter relation for rectangular ducts.

Disclaimer

Estimate only. Type the model’s sensible recovery. A range hood and a dryer are separate exhausts.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.