Free BTU to CFM Calculator. required airflow from a sensible BTU/h and a temperature difference (inverse of 1.08). Runs in your browser; not a permit or a Manual J.
Estimate only. Use the adopted mechanical code, nameplate curves and a licensed designer. Not Manual J, not a listed hood, not electrical sizing.
This page converts required airflow from a sensible BTU/h and a temperature difference (inverse of 1.08). It is the BTU to CFM tool in the heat group on ACH Calculator.
It is not a latent-inclusive enthalpy CFM or a duct sizer (take CFM there next). If you need those, open a related tool instead of stretching this identity.
The identity on screen is CFM = q_s / (1.08 × ΔT). Adjacent pages keep their own inputs so you do not mix a bath-fan table with a 62.2 dwelling rate or a duct-friction takeoff.
Related calculators on this site:
Use the fields that match the job: BTU/h or kW, ΔT, result CFM and L/s. Press Example to load the worked numbers. Clear empties the form. Related tools in the Next bar reuse CFM, ACH, temperatures and flows you already typed on this device.
Values update in this browser as you type. Use Example for the same numbers as the worked section. Copy puts the result on the clipboard. Next links reuse the last CFM, ACH and temperatures you typed on this device.
CFM = q_s / (1.08 × ΔT)
Reject zero or negative lengths, areas, flows, pressures and absolute temperatures. ACH above about 120 is allowed for tents and cleanrooms but is flagged as unusual for occupied rooms. The 1.08, 0.68, 500 and 24 factors assume near-standard air or water; override density when you are in Denver or on glycol.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
Typical uses include:
1) 12,000 BTU/h at 20 °F → 556 CFM.
2) Reheat 5,000 BTU/h at 15 °F.
3) Radiator is water-side — use gpm-btu.
If the job is life-safety, sterile, or listed equipment, stop here and use the specification.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
The Example button uses this set:
q=12000
ΔT=20
CFM=12000/(1.08×20)=556
Work the same arithmetic on paper; the live result should match within rounding.
No. Total capacity / (1.08 ΔT) overstates CFM if part of capacity is latent.
Smaller ΔT needs more CFM. Coils and comfort set ΔT.
1 kW = 3412 BTU/h.
Airside CFM is this page. Waterside is gpm-btu.
Open cfm-per-ton when you think in tons, not ΔT.
Use absolute ΔT. Direction is heating vs cooling.
Primary identity: CFM = q_s / (1.08 × ΔT). Interpret it with the sources listed below, not as a photocopy of a copyrighted table.
Estimate only for BTU to CFM. Adopted mechanical codes, OEM curves and a licensed designer prevail.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size refrigerant charge, fire dampers, medical gas, or electrical conductors.