ASHRAE 62.2 is a dwelling-ventilation standard. The arithmetic most US web tools publish for the 2016-and-later IP fan is Q_fan = 0.03 × A_floor + 7.5 × (N_br + 1), with area in square feet and Q in CFM. A 2,000 ft², 3-bedroom house is 0.03 × 2000 + 7.5 × 4 = 60 + 30 = 90 CFM. That fan is meant to dilute the dwelling, not to dry a shower stall.
Earlier 62.2 years used different coefficients. Infiltration credits, weather factors and local amendments change the installed CFM. This site does not compute Qinf and does not reprint the standard’s tables. Type the area and bedroom count you would put on a 62.2 worksheet, then treat the result as the identity, not a stamped design.
What to open
Whole-house 62.2 holds the form. Do not open bathroom-fan and add 50 CFM per bath into this number — baths are local exhaust. Do not open ACH to CFM and type 0.35 ACH on the whole volume unless your spec literally says that; 0.35 ACH on 16,000 ft³ is 93 CFM, which can look similar to 62.2 by coincidence and still be the wrong identity on a different house.
After you have Q_fan, a long duct run still needs static pressure and a fan that delivers that CFM at the real ESP. Open fan actual and duct size next.
Worked numbers
1,200 ft², 2 bedrooms: 0.03 × 1200 + 7.5 × 3 = 36 + 22.5 = 58.5 CFM. A “50 CFM bath fan always on” is not a substitute unless the layout, noise, and makeup path were designed that way.
3,400 ft², 5 bedrooms: 0.03 × 3400 + 7.5 × 6 = 102 + 45 = 147 CFM. That is a dedicated ERV/HRV or in-line fan conversation, not a ceiling bath fan.
FAQ
Does 62.2 replace a kitchen hood?
No. Range-hood CFM and makeup air are separate. 62.2 is dwelling outdoor air.
Continuous versus intermittent?
The form above is a continuous-fan rate. Intermittent fans need a runtime factor from the adopted year — not calculated here.
Conditioned floor area?
Use the area 62.2 tells you to use for that year (typically conditioned floor area, not garage, not unconditioned basement unless the year says so).
ACH50 credit?
Optional in some years. This page does not apply it. Open ACH50 only as a tightness sketch.
SI?
Some 62.2 SI forms exist in the standard. The live tool is the IP identity with unit chips for display.
Limits
Local IRC/IMC adoption, 62.2 year, and an ERV listing override this sketch.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.