All calculators

Open a tool for the identity that matches the job: air, duct, fan, heat, moisture or water.

Air

ACH to CFMRoom air changes per hour into supply or exhaust airflow in cubic feet per minute (and the reverse).Bathroom fan CFMA residential bathroom exhaust rate using the IMC-style 50/20 CFM chips or a volume×ACH check.Range hood CFMRange-hood airflow from hood length, face velocity, or a typed CFM — not from kitchen ACH.ASHRAE 62.2A dwelling mechanical ventilation rate using the ASHRAE 62.2 floor-area plus bedroom count identity.ASHRAE 62.1 OABreathing-zone outdoor air from 62.1 people and area rates you type (Rp, Ra, Pz, Az).Makeup airHow much dedicated makeup airflow you still need after subtracting the exhaust you typed and an allowed uncompensated amount.Garage exhaustA residential or small garage exhaust sketch from ACH or CFM per square foot.Attic ventilationA net-free attic ventilation area sketch using 1/150 or 1/300 of attic floor area.Cleanroom ACHCleanroom supply CFM from a user-selected air-change target associated with an ISO class name.Grow tent CFMGrow-tent exhaust from tent volume, a target air-change rate, and an optional carbon-filter derate.CADR air changesAir-cleaner air changes from AHAM-style CADR and room volume (or the reverse CADR need).ACH50 to ACHA crude natural infiltration estimate from a blower-door ACH50 and a user n-factor.Parking garage CFMAn enclosed parking-garage exhaust sketch from ACH or CFM per area — with CO demand-control called out as not modeled.CFM per roomSplit system CFM across rooms by weighted floor area, then count registers at 120 CFM each.Commercial exhaust CFMRoom exhaust from a user-typed per-fixture or per-area rate — not a reprinted occupancy table.Commercial kitchen hoodType I unlisted wall or island canopy: Q = hood length × CFM per foot by cooking duty.Dryer exhaust and makeupAdd dryer + hood + baths that can run together; flag makeup when the hood > 400 or the dryer > 200 CFM.Whole-house fanCFM = floor area × CFM/ft², scaled by ceiling height over 8 ft. Attic net free area is CFM/750.Evaporative coolerCFM = (floor area × ceiling height) / minutes per air change.Attic fanCFM = attic floor × 0.7, or × 0.805 for a dark or steep roof.CO₂ to CFMOutdoor CFM per person = generation / ((indoor ppm − outdoor ppm) / 1,000,000).ERV / HRV heatVentilation from floor area and bedrooms, then recovered heat = 1.08 × CFM × ΔT × effectiveness.

Duct

Duct sizeRound or rectangular duct size from CFM and a target velocity, or from a user equal-friction rate.Duct velocityMean duct velocity from airflow and cross-section (round diameter or W×H).Equivalent round ductHuebscher equivalent round diameter of a rectangular duct so friction comparisons stay honest.Duct frictionStraight-duct pressure drop from a typed friction rate or a Darcy-Weisbach sketch with user roughness.Fitting lossA fitting pressure drop from a user loss coefficient C and velocity (dynamic pressure).Duct offsetThe centerline length and run of a duct offset given rise and fitting angle — HVAC geometry, not electrical conduit.Static pressureA fan external static budget by adding the pressure drops you type.Total equivalent lengthPressure drop from total equivalent length and a friction rate — the residential TEL method.Duct aspect ratioAspect ratio of a rectangular duct and the equivalent diameter penalty as AR grows at constant area.SCFM to ACFMActual cubic feet per minute from standard CFM using the temperatures and pressures you type.Air densityMoist or dry air density from temperature, pressure or altitude so 1.08 and fan power stay honest.Return grille sizeReturn (or supply) grille size from CFM, face velocity, and a free-area fraction.Supply register sizeStock floor or ceiling register from room CFM, face velocity and free-area share.Friction rate from ESPAvailable static pressure after coil, filter and fittings, then FR = ASP × 100 / TEL.Duct transition lengthMinimum centered reducer length from wall angle: L = max(ΔW, ΔH)/2 / tan(θ).

Fan

Heat

Sensible heatSensible heating or cooling rate of an airstream from CFM and dry-bulb difference.Latent heatLatent cooling (or humidification) rate from airflow and a humidity-ratio difference.Mixed-air temperatureMixed-air dry bulb (and optional humidity ratio) from two airstreams, typically OA and return.BTU to CFMRequired airflow from a sensible BTU/h and a temperature difference (inverse of 1.08).Cooling tonsCooling tons from BTU/h or kW, and the reverse.CFM per tonAirflow from cooling tons using the 400 CFM/ton family of rules you can edit.AC sizeA crude residential air-conditioner capacity from floor area — labeled as not Manual J.Heating loadA crude winter heating load from area and a user BTU/h·ft² or a UA×ΔT sketch.Furnace sizeFurnace input and output from a heating load and AFUE (and an optional oversize pickup).Heat-pump sizeA comparison of cooling tons and heating BTU/h so you can see which one governs a heat-pump pick.Mini-split BTUA room-level ductless capacity sketch from area and a BTU/h per square foot chip.Chiller tonnageEvaporator (or condenser) tons from chilled-water flow and ΔT.Ventilation loadOutdoor-air sensible plus latent load from OA CFM and indoor/outdoor psychrometric states.Heat-pump balance pointAn outdoor-temperature balance point from a linear load line and a linear heat-pump capacity line you type with two points each.Makeup-air heatingWinter MAU output q = 1.08 × CFM × (T_supply − T_outdoor) × share.Furnace temperature riseΔT = supply − return; CFM = output / (1.08 × ΔT); check the nameplate 35–65 °F band.Window SHGC heat gainSolar gain q = SHGC × area × irradiance × (1 − shade fraction).AC running costWatts = BTU/h ÷ the efficiency number. Cost = kW × hours × duty × your price.Combustion air openingFree area per opening = input ÷ the rate you pick. Gross opening divides by the louver’s free area.Baseboard lengthElectric feet = (BTU/h ÷ 3.412) ÷ W/ft. Hot-water feet = BTU/h ÷ the element’s BTU/h per foot.Baseboard from the roomWatts = room area × W/ft². Length = watts / 250.

Moisture

Water

Charts

Guides

What ACH meansACH is a rate against a box volume. It is not a fan nameplate, not a dwelling ventilation credit, and not capture velocity at a hood.ASHRAE 62.2 dwelling ventilation62.2 sizes a dwelling mechanical ventilation fan from conditioned floor area and bedrooms. It is not a bath fan and not room ACH.ASHRAE 62.1 outdoor air62.1 outdoor air is occupancy plus floor area. It is not dwelling 62.2 and not a recirculated ACH.Bathroom exhaust versus ACHA dwelling bath is not sized as “kitchen ACH.” Most US talk starts at 50 CFM intermittent or 20 CFM continuous, then checks area, fixtures and 8 ACH.Duct velocity and noiseVelocity is CFM divided by free area. High fpm is noise, fitting loss, and a fan that never hits nameplate CFM.Equal-friction duct sizingEqual friction keeps a target pressure drop per 100 ft. It is a sketch, not Manual D.Fan laws in the fieldFan laws are ratios. They do not replace a fan table at a new static pressure.Where 1.08 comes from1.08 is standard-air shorthand, not a law of nature.400 CFM per tonCFM/ton sets evaporator airflow once you already have tons. It does not tell you how many tons the house needs.Psychrometric statesTwo independent properties fix moist air. The third is calculated. A copyrighted ASHRAE chart image is not on this site.The 500 constantAir uses 1.08. Water uses 500. Mixing them is the usual hydronic takeoff error.Makeup air after a hoodA 1,200 CFM hood does not get 800 CFM of makeup from a 400 CFM “credit.” Ranking code talk treats 400 as a threshold, then makeup ≈ exhaust.

What this calculator does

This page is the full list of airflow, duct, fan, coil, psychrometric and hydronic calculators. Open a name to run that identity.

Nothing is calculated on this index. Each tool page holds one formula. Charts and guides sit in their own libraries.

How to use it

Scan the groups or use search. Air is ACH and outdoor air. Duct is size and pressure. Fan is laws and capture. Heat is 1.08 and tons. Moisture is psychrometrics. Water is GPM × ΔT.

Pick the page whose units match the job. Do not stretch room ACH into a 62.2 dwelling rate or a hood capture velocity.

Formula, units, and limits

There is no single formula here. Typical identities: CFM = ACH × V / 60; 62.2 Q = (CFA × 0.03) + 7.5(Nbr+1); Huebscher De; fan laws; qs = 1.08 × CFM × ΔT; GPM = BTU/h / (500 × ΔT).

Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.

When you would use it

Use this list when you know the quantity (CFM, GPM, dew point) but not which URL holds it.

None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.

Worked example

Need CFM from a bedroom box → ACH to CFM. Need 50 CFM for a bath → bathroom fan. Need outdoor air for people + area → 62.1.

Need round duct from 400 CFM at 700 fpm → duct size. Need coil water from 40,000 BTU/h at 20 °F → GPM-BTU.

FAQ

Why so many pages?

Each identity has different inputs. Mixing bath 50 CFM with 62.2 or with duct friction hides mistakes.

Where is Manual J?

Not on this site. Heat pages are 1.08 / 400 CFM/ton sketches, not a load takeoff.

Charts versus tools?

Charts are short lookups. Tools take your numbers.

Guides?

Guides only say which tool to open.

SI units?

Yes, on each tool.

Does search filter this list?

On the home page, yes. This page shows every ready tool.

References

Disclaimer

A directory is not a design. Open the matching calculator and read its limits.

Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.