| Use | fpm sketch | m/s |
|---|---|---|
| Residential supply trunk | 600–900 | 3.0–4.6 |
| Residential return trunk | 500–700 | 2.5–3.6 |
| Commercial main | 1000–1500 | 5.1–7.6 |
| Quiet register / grille face | 300–500 | 1.5–2.5 |
| Return grille free-area talk | ~300 | ~1.5 |
400 CFM in 10 in round is about 730 fpm (residential supply). 400 CFM in 6 in round is about 2,040 fpm (noise). Open duct velocity to invert Q, V and D, and duct size for 0.08 in/100 ft equal friction.
Face velocity on a grille is not trunk velocity. A 300 fpm return face needs much more area than a 700 fpm trunk carrying the same CFM.
FAQ
Why list m/s?
European specs often quote 3–5 m/s in occupied-branch ducts.
Kitchen grease?
Listed grease ducts have their own velocity and slope rules. Not this table.
Flex?
Treat flex as slower / higher friction than smooth metal at the same Q.
VAV maximum?
Use the maximum box CFM, not the minimum, when checking noise.
Can I exceed 1,500 fpm?
Some risers do. Budget fan power and silencers. This table is talk, not a license.
Limits
Not an NC catalog and not a fire-smoke damper schedule.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.