Space (discussion)ACH sketchWhat to open instead if this is the wrong job
Living / office mixing2–662.1 outdoor air if you needed OA, not mixing
Bedroom2–4Mini-split BTU if you meant cooling
Bathroom (ACH check only)6–10Bathroom fan (50/20 + HVI + 8 ACH)
Kitchen dilution (not a hood)6–12Kitchen hood CFM per foot / BTU
Residential garage4–8Parking garage 0.75 CFM/ft² for structures
Hobby grow tent~60 (1 / min)Grow-tent tool with filter extra
ISO 8 planning talk15–25ISO particle limits are not ACH
ISO 7 planning talk30–60Same caveat

ACH only means something with a volume. 6 ACH in an 8 ft office cubicle is a handful of CFM; 6 ACH in a gym is a huge fan. After you pick a row, open ACH to CFM and type the real box. The tent row is one exchange per minute on the tent page, not 6 ACH.

Healthcare, laboratories and smoke control use other documents (for example ASHRAE 170 for many clinical spaces). Those rates are not this table.

Worked numbers

Bedroom 12 × 14 × 8 ft, 3 ACH → 67 CFM. That is mixing, not 62.2. Office 20 × 40 × 10 ft, 4 ACH → 533 CFM supply; outdoor air for the occupants is still the 62.1 page.

FAQ

Can I average the band?

If the spec is silent, pick a value and document it. Do not invent 3.7 ACH for SEO.

Why tents show 60?

Hobby odor/heat talk is about one volume per minute. Lights and carbon filters add more on the tent tool.

ISO row legal?

No. ISO 14644 is particles. ACH is a planning leftover from older FS-209 talk.

Kitchen 12 ACH versus a hood?

Dilution is not capture. Size the hood first.

SI?

ACH is independent of units. Volume units must match the flow units on the tool.

Limits

Not IMC parking ventilation, not an OR, not a prison cell standard.

Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.