Water-side heat is q = ṁ c_p ΔT. In US gallons: 8.33 lb/gal × 60 min/h × 1 BTU/lb·°F = 500, so q_BTU/h = 500 × GPM × ΔT_F. 10 GPM through a 20 °F drop is 100,000 BTU/h. Invert: GPM = q / (500 ΔT). A boiler loaded at 80,000 BTU/h and 20 °F ΔT wants 8 GPM of water, not 8 CFM of air.

Glycol lowers c_p and raises viscosity. Shops often type 400–450 instead of 500. Cooling tons on water are tons = GPM × ΔT / 24 because 12,000 / 500 = 24. Pipe size is velocity: Type L copper at about 2–4 fps on this site, v = 0.4085 GPM / ID², not the air duct tool.

What to open

GPM to BTU, chiller tonnage, hydronic pipe, boiler size, expansion tank for Ve and Vt. Air-side 1.08 stays on sensible-heat.

FAQ

Closed loop lift?

Fill height is not pump head once the loop is full. Pump the friction and the coil drop on pump-head.

ΔT 10 versus 20?

Half the ΔT doubles GPM for the same load — pipes and pumps grow.

Steam?

Wrong constant. These pages are liquid water.

Antifreeze volume?

Expansion e is larger than water. Raise e on the expansion-tank page; do not keep 500 blindly on the coil.

Buffer tank?

Volume for runtime, not the 500 identity. Different job.

Limits

Not a pump-curve picker and not an ASME vessel stamp.

Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.