| Talk | fpm |
|---|---|
| Canopy face (discussion) | 50–100 |
| Open paint booth face | 100 (some 60–125) |
| Slot hood (much higher) | 1,000–2,000 |
Q = V × A. A 2 × 3 ft opening at 100 fpm is 600 CFM. A paint booth 8 × 7 ft at 100 fpm is 5,600 CFM, which then needs makeup. Open capture velocity and paint booth. Kitchen hoods on this site use CFM/ft and BTU/100, not this canopy table, unless you intentionally switch to face area.
FAQ
OSHA 100 fpm?
A widely cited open-booth face talk. Confirm the current rule and the listing.
Flanges?
A flange can cut required Q. Not modeled; type a lower V if the design says so.
Distance to the source?
Capture dies fast with distance. This identity assumes the opening is the capture plane.
Welding?
Often a different ACGIH figure. Not this table.
Duct after the hood?
Use duct-velocity / duct-size on the exhaust CFM.
Limits
Not an ACGIH VS-print reprint and not a listed kitchen hood.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.