| Face | fpm |
|---|---|
| Quiet return (free area) | 300–400 |
| Filter grille | 300–500 |
| Too noisy / bypass risk | > 500 |
A_free = Q / V. A_nom = A_free / (free-area fraction). 800 CFM at 300 fpm is 2.67 ft² free; at 70% free area, 3.81 ft² nominal ≈ 548 in². Open return grille for stock sizes and multiple grilles.
FAQ
MERV 13?
Thicker filters cut free area and raise ΔP. Use the submittal FA% and add ΔP on static-pressure.
Supply registers?
Same identity; throw is catalog data.
Closet return?
Often too small and too fast. That is a noise complaint, not a badge of good design.
Filter in the air handler only?
Then the grille can be more open, but the filter rack still has a face-velocity limit from the OEM.
SI?
1.5 m/s is roughly 300 fpm.
Limits
Not a manufacturer NC or pressure-drop curve.