Inch-pound sensible heat in an airstream is q_s = 60 × ρ × c_p × CFM × ΔT. Plug ρ ≈ 0.075 lb/ft³ and c_p ≈ 0.24 BTU/lb·°F and you get 60 × 0.075 × 0.24 ≈ 1.08. So q_s ≈ 1.08 × CFM × ΔT at sea-level dryish air. 400 CFM through a 20 °F split is 8,640 BTU/h, a bit under one cooling ton of sensible capacity.
Denver air is thinner. If density is 0.062, the factor is about 0.89. Using 1.08 there overstates coil capacity. Wet coils also pull latent heat; that is 0.68 × CFM × Δgrains on latent heat, not 1.08. Water in a pipe is 500 × GPM × ΔT — never 1.08.
What to open
Sensible heat for the 1.08 form. Air density for altitude. BTU to CFM inverts to CFM = q / (1.08 ΔT). Ventilation load adds sensible and latent on outdoor air.
Worked numbers
1,200 CFM OA, 90 °F outdoor to 75 °F room, ΔT = 15 °F: q_s ≈ 1.08 × 1200 × 15 = 19,440 BTU/h. Add latent if humidity is high. That OA load is on top of room loads, not instead of them.
FAQ
SI factor?
About 1.21 × L/s × ΔT_K for standard air, or 1.23 × L/s × ΔT_K in some textbooks. Use the tool’s SI chip.
Is 1.10 better?
Some shops use 1.10. It is still a density assumption. Type a factor only if you mean it.
Room load versus coil load?
1.08 on supply CFM and supply-to-room ΔT is coil sensible, not a Manual J envelope load.
Glycol?
Wrong page. Open GPM-BTU and derate 500.
Electric heat?
kW × 3412 = BTU/h, then CFM from 1.08 if you need a rise.
Limits
Not Manual J. Not a refrigerant enthalpy-in/enthalpy-out coil selection.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.