Air speed in a duct is V_fpm = CFM / A_ft². A 10 inch round duct has area π(5/12)² ≈ 0.545 ft². 400 CFM in that duct is about 730 fpm. That sits in the usual residential supply band (roughly 600–900 fpm). The same 400 CFM forced through a 6 inch round (~0.196 ft²) is about 2,040 fpm — a whistle, a fitting-loss spike, and a static-pressure problem.

Returns run slower than supplies in houses (often 500–700 fpm in the trunk, 300 fpm at a grille face) because the grille is in occupied space. Commercial mains may be 1,000–1,500 fpm if the mechanical room can take the noise. None of these bands replace a manufacturer NC catalog.

What to open

Duct velocity inverts Q, V and diameter. Velocity bands are discussion rows. Return grille uses 300 fpm free-area talk, not trunk fpm. After velocity looks high, open duct size on equal friction instead of shrinking the pipe to “make it fit.”

Worked numbers

800 CFM return at 300 fpm needs 2.67 ft² free area. At 70% free area the grille is about 3.81 ft² nominal (548 in²) — a large filter grille, or two grilles, not a 10×6 return.

FAQ

Face velocity versus neck velocity?

Face is at the grille. Neck is the collar, often faster. Size noise on the face; size the duct on the neck/trunk.

Flexible duct?

Corrugation raises friction and can raise effective velocity pressure. Use a higher friction rate on duct-size.

SI?

1 m/s ≈ 197 fpm. 4 m/s is a common European residential talk, near 800 fpm.

Can I fix noise with a bigger fan?

Usually no. You need more area or less CFM at that register.

Fire damper?

A damper is extra ΔP, not a velocity band. Add it on static-pressure.

Limits

Not an acoustic laboratory rating and not a kitchen-grease duct listing.

Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.