Air changes per hour (ACH) answers one question: if this room were a sealed box, how many times would its volume leave and be replaced in sixty minutes? The identity is CFM = ACH × Volume / 60 with volume in cubic feet. A 12 × 14 × 8 ft bedroom is 1,344 ft³. At 6 ACH that is 134 CFM. The same 134 CFM in a 4,000 ft³ living room is only 2 ACH. The number is meaningless until you state the box.
People mix ACH with three other CFM jobs. A dwelling fan sized on ASHRAE 62.2 uses floor area and bedrooms, not room ACH. A bathroom intermittent fan is often a 50 CFM table value, then an 8 ACH check on a large bath. A range hood is CFM per foot of cooktop or burner BTU/h, never kitchen ACH. Opening the wrong page will still print a CFM, and that is how a 6 ACH “kitchen ventilation” undersizes a hood.
How to use the ACH to CFM tool
Type length, width and height, or type volume directly. Enter ACH to get CFM, or CFM to get ACH. Switch feet and metres, and CFM / m³/h / L/s, on the unit chips. Press Example for the 12 × 14 × 8 ft, 6 ACH set. Then change one dimension so you see the flow move with volume.
Open ACH to CFM for the arithmetic. Open room ACH ranges only for discussion bands (bedroom 2–4, office 2–6, hobby tent near one exchange per minute). Those bands are not code.
Worked numbers
Office 20 × 30 × 10 ft = 6,000 ft³. Sketch 4 ACH → 400 CFM supply if you were mixing the whole volume. That 400 CFM is not outdoor air. Outdoor air for ten people in 600 ft² of office is the 62.1 form on outdoor air: Rp × people + Ra × area. Mixing CFM and outdoor-air CFM in one duct schedule is a common takeoff error.
Grow tent 4 × 4 × 6.5 ft = 104 ft³. One exchange per minute is 104 CFM before a carbon-filter extra. That is the tent tool, not 6 ACH on the room-ACH chart.
FAQ
Is ACH the same as outdoor-air fraction?
No. ACH can be 100% recirculated air. Outdoor-air fraction is a different ratio on the mixed-air and 62.1 pages.
Why divide by 60?
ACH is per hour. CFM is per minute. Sixty minutes convert the same volume flow.
Can I use ACH for a whole house?
Only if you mean whole-house volume × ACH. 62.2 is the usual dwelling fan identity and is usually a much smaller CFM.
Does infiltration count?
Not in this identity. ACH50 / n is a tightness sketch on its own page.
SI form?
Q in m³/h = ACH × V_m³. Q in L/s = ACH × V / 3.6.
Limits
Do not treat a room ACH sketch as a hospital OR rate, a cleanroom ISO particle limit, or a smoke-control design.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.