Equal-friction sizing picks a friction rate f (inches of water per 100 ft) and solves a round diameter that carries the CFM at that rate. A common residential talk is 0.06–0.10 in/100 ft; this site defaults to 0.08, which is where several ranking duct tools sit. A published IP fit used here is d = (0.109136 × Q^1.9 / f)^(1/5.02) with d in inches and Q in CFM. 400 CFM at 0.08 lands near 8. something inches; you then buy the next stock round (8, 9, 10…).
Rectangles use Huebscher equivalent diameter De = 1.30 (a b)^0.625 / (a + b)^0.25. The tool can hold one side at 8 inches and grow the other until De matches the round. Aspect ratio above about 4:1 wastes metal and raises friction; that is the aspect-ratio page.
What to open
Duct size is the live solver. Optional velocity is a check, not the default method — ranking pages lead with friction, then show fpm on the stock size. Friction-rate chart lists quiet residential versus commercial mains. Fitting extra length belongs on TEL and fitting loss.
Worked numbers
400 CFM, f = 0.08: round De from the fit, stock often 9 or 10 in depending on rounding, actual velocity on the stock area. A 8 × ? rectangle matching that De is wider than 8 if you freeze height at 8 in.
FAQ
Is this Manual D?
No. Manual D uses a full takeoff, available static, and room-by-room CFM. This is one branch identity.
Why not size only on 700 fpm?
Velocity-only sizing ignores how long the run is. Equal friction keeps pressure drop in a band.
Flex duct?
Use a higher f or a listed flex chart. Smooth-pipe f under-sizes flex.
Metal versus duct board?
Roughness changes f. Type the rate your spec uses.
Next after diameter?
Fittings, TEL, fan ESP, then a fan that delivers Q at that ESP.
Limits
Not a grease duct, not a lab exhaust manifold, not a manufacturer pressure chart.
Estimates only. Adopted mechanical code, nameplate curves, TAB readings and a licensed designer prevail. This is not Manual J, not a listed-hood submittal, and not a permit drawing.